ComputeFinder

Tools / Power

What does 100MW mean?

Turn a megawatt figure into energy, racks and accelerator counts. Every assumption is shown and you can change it.

Illustrative arithmetic, not a measurement. The numbers below follow from the assumptions on this page. The assumptions are our own round figures for illustration. They are not sourced facts about any real site, chip or operator, and real sites differ widely.

Your figure and assumptions



From 0.01 to 100,000.



IT load is the power reaching the computing equipment. Facility load adds cooling and losses. A grid connection is usually quoted in MVA.

Assumptions you can edit



Assumed 1.3. Allowed 1 to 3.



Assumed 0.95. Allowed 0.5 to 1.



Assumed 80. Used for annual energy. Allowed 1 to 100.



Assumed 40. Dense AI racks can be far higher, older racks far lower.



Assumed 70. The rest is storage, networking and general servers.



Assumed 8. Whole number, 1 to 72.



Assumed 6. Gives the high end of the GPU range.



Assumed 14. Gives the low end of the GPU range.

Reset

What 100MW of it load comes to

Illustrative arithmetic, not a measurement
WhatResultHow it was worked out
IT load100 MWYour figure.
Facility load130 MWIT load multiplied by PUE (1.3).
Overhead (cooling, power losses, lighting)30 MWFacility load minus IT load.
Equivalent in MVA at the assumed power factor137 MVAFacility load divided by power factor (0.95).
Energy in a year911 GWhFacility load x 80% average load x 8,760 hours.
Racks2,500IT load divided by 40 kW per rack.
Accelerator servers5,000 to 11,66770% of IT load, divided by 14 kW and 6 kW per server.
Accelerators (GPUs or similar)40,000 to 93,333Servers x 8 accelerators per server.

Ranges come from the two kW per server assumptions. Nothing here adds capacity across different metrics or sites: it is one figure worked through one set of assumptions.

The link holds your figure and every assumption, so anyone opening it sees the same arithmetic.

MW and MVA in plain English

A megawatt (MW) measures real power: the part that does useful work, such as running servers and cooling. A megavolt-ampere (MVA) measures apparent power: the total the wires and transformers have to carry. The two differ by the power factor, so MW is MVA multiplied by the power factor. At a power factor of 0.95, a 100MVA connection carries about 95MW of real power.

Grid connections and transformers are usually sized in MVA, while data centre loads are usually described in MW. When someone says "a 100MW data centre", ask which they mean: IT load, facility load or a grid connection, and whether the figure is MW or MVA. They can differ by a third or more. This is a general explanation, not a statement about any named project.